RL-HF-FR (-P) SELF-EXTINGUISHING HALOGEN FREE RIGID PIPE FOR ELECTRICAL INSTALLATION
Mechanical strength: 320N (light) 2
Impact resistance: 1,0 kg/100mm (light) 2
Temperature range (application, installation):
from -15°C to +110°C 3 3
Flexibility: rigid 1
Flammability: self-extinguishing HB (Ul94)
Material: special plastic
EU Designation (EN 61386-1): 22331
Application:
Rigid pipe is used for distribution and protection of cables in building and industrial electrical installations. Recommended for places, with an increased risk of fire hazard (wooden constructions, lofts, garrets, etc.) and tightened security against toxic chemical compounds (halogen free). It ensures high strength and resistance to mechanical factors. Pipe has ideally smooth surface.
Standard length of the rigid electro-installation pipes is 3 m.
Characteristics of material:
Free from halogen (phosphorus and cadmium) self-extinguishing/flame retardant, high-bending and crack resistance, well balanced elongation and elasticity behaviour as well as high abrasion-resistance,
Standard diameters
Nominal diameter DN (mm) | Inside diameter (mm) | Outside diameter (mm) | Quantity in bundle (m.) |
---|---|---|---|
13 | 11 | 13 | 60 |
16* | 14 | 16 | 60 |
18 | 16 | 18 | 60 |
20* | 18 | 20 | 60 |
22 | 20 | 22 | 60 |
25* | 22 | 25 | 60 |
28 | 25 | 28 | 45 |
32* | 29 | 32 | 30 |
37 | 33 | 37 | 18 |
40* | 36 | 40 | 18 |
* PN-EN 60423 diameters |
Resistance to selected chemical compounds
Acids | weak | high |
strong | high | |
oxidized | lack | |
hydrofluoric | medium | |
Bases | dry halogens | medium |
weak | high | |
strong | high | |
Solvents | alcohols | high |
esters | medium | |
ketones | medium | |
ethers | medium | |
chlorinated hydrocarbons | medium | |
Oil and diesel materials | benzene | medium |
petrol | medium | |
diesel mixtures | medium | |
mineral oils | high | |
fatty oils | high |
Places of Applications
Wall installations | recommended |
Sunk installations | admissible |
Outer wall installations | not allowed |
Plaster walls | recommended |
Combustible surfaces (wood, etc.) | recommended |
Underground installations | not allowed |
Poured concrete, vibrated concrete | not allowed |
Steamed and vibrated concrete | not allowed |
Electrotechnical equipment, industrial apparatus | admissible |
Control and automatics | admissible |
Food and chemical industry facilities | admissible |
Automotive industry | recommended |
Shipyard industry | recommended |
Aircraft industry | recommended |